Central HVAC Monitoring: From the Chiller Plant to Every Air Handler
The chillers are in the basement, the cooling tower is on the roof and the air handlers are spread across every floor. Our RIO remote I/O modules sit beside each one to collect signals and send control outputs, then connect back to the BMS in the control room over Ethernet.
RIO units beside each piece of equipment
The chiller plant, the cooling tower and the air-handling rooms are several floors apart. Each RIO unit sits next to its equipment, so field wiring only runs to the nearest unit. Every RIO then connects back to the control room over Ethernet (Modbus TCP), where the building's existing BMS reads it directly.

Chiller plant RIO
Chiller and pump status and start/stop, water temperatures and differential pressure
See the I/O layoutOne baseboard, a different module mix at each site
LLD-Modbus32E-01 has five general slots and one EXT expansion slot, filled with DI, relay, AI, AO and other modules to match the signals on site. Select a module to see what it is wired to.

| Slot | Module | Ch. | Signal |
|---|---|---|---|
| Module 01 | |||
| CH1 | Fan 1 running | ||
| CH2 | Fan 1 fault | ||
| CH3 | Fan 2 running | ||
| CH4 | Fan 2 fault | ||
| Module 02 | |||
| CH1 | Fan 1 start/stop | ||
| CH2 | Fan 2 start/stop | ||
| Module 04 | |||
| CH1 | Tower outlet water temp. | ||
| CH2 | Tower inlet water temp. | ||
| CH3 | Spare | ||
| CH4 | Spare | ||
Example layout: "Chiller 1/2" and "Fan 1/2" only illustrate channel allocation. Actual modules and point counts depend on the equipment on site.
Control rules live in RIO
LLD-Modbus32E-01 supports LLD-DDC direct digital control, so decisions are made by RIO on site.
Cooling tower fans: start and stop by water temperature
The start and stop thresholds are set separately (hysteresis), together with a minimum run time. When the water temperature hovers around a threshold, the fans do not keep starting and stopping.

Equipment used
LLD-Modbus32E-01
REMOTE I/O- 5 general slots + EXT expansion slot, up to 32 I/O points
- Ethernet ×1 + RS-485 ×2; connects to the BMS over Modbus TCP
- Supports LLD-DDC for on-site control
Flexible I/O module selection
I/O MODULES- Fit DI, DO, relay, AI and AO modules to the signals on site
- This application uses ModIO-DI, Relay, AI, AO and 12DI
- The AI module accepts 4–20 mA, 0–10 VDC and NTC signals
- The EXT expansion slot takes a 12-point DI or DO module
HVAC equipment and sensors
ON SITE- Chillers, pumps, cooling tower, air handlers
- VFDs, chilled-water valves
- Water temperature, temperature/humidity and differential-pressure sensors
Questions before you start

Do the chillers need a Modbus interface?
No. Wiring the chillers' run, fault and start/stop contacts, plus water temperature sensors, is enough to monitor them. The DI modules take wet-contact inputs, so the 5–24 VDC loop supply is provided on site.
Our BMS is from another vendor. Can it read RIO?
RIO uses standard Modbus TCP, so any BMS that supports Modbus can poll it directly.
The cooling tower is on the roof. Do we run cables to the basement?
No. RIO installed on the roof collects signals and controls the fans locally, so only one network cable runs back to the control room, which keeps wiring costs down.
What if each floor's air handler has a different point count?
Fit the modules to that floor's signals; if the points exceed one baseboard, add another unit. You can estimate the count with the calculator in our remote I/O module article.
Which sensor signals are supported?
The AI module accepts 4–20 mA, 0–10 VDC and NTC signals.
How is the DDC logic configured?
The control logic is written with the ICDT graphical control compiler and runs on RIO.
Every building's HVAC is different
The number of chillers, pumps and air handlers, their I/O points and the DDC control rules can all be planned for your site. Tell us about your building's equipment, and our sales team will help assess your needs.