Filter pressure switch
Trips when the pressure drop across the filter exceeds the setpoint, signaling that the filter needs changing.

Remote I/O puts the I/O points in the field and reports back to the controller over a single RS-485 or network cable. Using an air handler as a real-world example, see which signal each sensor and actuator uses, then estimate how many modules you need.
There is one controller, but sensors and actuators are spread across floors and plant rooms. Remote I/O moves the terminals next to the equipment, converts field signals into Modbus data there, and sends them back over a single RS-485 or network cable.









Click a device on the drawing or a card below to see which signal it sends or receives and which module it connects to.

Trips when the pressure drop across the filter exceeds the setpoint, signaling that the filter needs changing.
Measures room air returning to the unit, typically an NTC or a 4–20 mA transmitter.
Measures discharge-air temperature; it is the feedback for the chilled-water valve loop.
Starts and stops the supply fan through an interposing relay or contactor.
Sends a position command to the damper actuator to set how much outdoor air comes in.
Modulates chilled-water flow through the coil to control supply-air temperature.
Sends a frequency command to the fan VFD to adjust airflow.
A signal coming from the field into the controller is an input; one going out from the controller is an output. A signal with only two states (on/off) is digital; one that varies continuously is analog.
Matching modules in this series: DI → ModIO-DI, ModIO-12DI; DO → ModIO-DO, ModIO-Relay, ModIO-12DO; AI → ModIO-AI, ModIO-AI+; AO → ModIO-AO, ModIO-AIAO. All fit the module slots of the LLD-ModbusIO and LLD-Modbus32E series.
A field contact closes or opens and the module reads it as 1 or 0 — it tells you what state something is in.


The controller issues a command and the module switches the output on or off. Large loads go through a contactor; small loads can be driven directly.


A sensor turns a physical quantity into current, voltage or resistance and the module measures it — it tells you how much.


The controller computes a proportion and the module outputs the matching voltage or current — it sets how far something opens.


Enter the point counts from your I/O list to see the modules and base units you need.
STEP 01 / 04
Sort each point on your I/O list into the five types below and enter the counts. Split DO by load: open collector for small DC loads, relay for AC or loads that need isolation.
STEP 02 / 04
How the remote I/O reports back to the controller or SCADA decides which base unit you need.
STEP 03 / 04
No points entered yet — go back to step 1 and fill them in.
This estimate leaves out the optional EXT slot (ModIO-12DI / 12DO) and ModIO-AIAO; confirm the final configuration with the configurator and our sales team.
STEP 04 / 04
Your point counts and uplink are filled into the email automatically; we will check the configuration and reply with a recommendation.
The DI modules in this series are sinking inputs, so pair them with 3-wire PNP (sourcing) sensors.
The sensor decides, not the module: if the sensor outputs 4–20 mA, set the input to 4–20 mA; if it outputs 0–10 V, set 0–10 V. ModIO-AI is switched with on-module jumpers. If the sensor offers both, 4–20 mA holds up better over long runs and in noisy environments.
The DI modules in this series take wet-contact inputs: the field provides the 5–24 VDC loop supply and the module does not power the contact, so a dry contact cannot connect directly. PNP (sourcing) sensors are recommended.
Remote I/O only carries signals and leaves the logic to the controller; a DDC runs its own control program. This series supports LLD-DDC, so control logic can run on the base unit itself.
Full comparison on the product line page