A small drainage pumping station in the late afternoon: a concrete equipment room with an antenna at the corner of the roof, two discharge pipes running over the levee and a utility pole beside them
SOLUTIONS · REMOTE SITES

Getting Data Back from Remote Sites with No Network Cable — A Wireless Monitoring Architecture

Unattended water facilities such as pumping stations and water gates often have no network cable. Using a small drainage pumping station as an example, this article shows how our CGate gateway, fitted with an optional cellular module and antenna, sends water level and power meter readings back.

Published
ARCHITECTURE WALKTHROUGH

System architecture at a glance

The camera moves from outside the station to the antenna, then into the control panel. Images are illustrative renderings; the actual layout depends on the site.

A small drainage pumping station with its equipment room, wet well and discharge pipes running over the levee, and an antenna at the edge of the equipment room roof (illustrative rendering)
Wireless link
Antenna
Equipment room: CGate in the control panel

For sites with limited connectivity

Where a site has no Ethernet connection, running a cable is impractical or network access is restricted, CGate can be fitted with the optional cellular module to send the data back wirelessly.

No Ethernet connectionHard to run a cableRestricted network
A small drainage pumping station with its equipment room, wet well and discharge pipes running over the levee, and an antenna at the edge of the equipment room roof (illustrative rendering)
Wireless link
Antenna

For sites with limited connectivity

Where a site has no Ethernet connection, running a cable is impractical or network access is restricted, CGate can be fitted with the optional cellular module to send the data back wirelessly.

No Ethernet connectionHard to run a cableRestricted network
Close-up of an antenna at the edge of the equipment room roof, with the extension cable running down the wall and into the room (illustrative rendering)
Antenna outside the panel
Back to CGate

Antenna included, and it can be extended

CGate stays in the control panel. If the signal inside the panel is weak, an extension cable can take the antenna outside the panel (extension cable supplied separately to suit the site).

Antenna includedTakes an extension cable
A CGate-06 gateway and wiring on the DIN rail inside the control panel, with the antenna extension cable running up and out of the panel (illustrative rendering)
CGate + cellular module
RS-485: level sensors, power meters

A reading beyond your limits triggers a notification right away

CGate polls RS-485 devices such as water level sensors and power meters. When a reading goes beyond the limits you set, it notifies you by email, LINE or other messaging, and the optional cellular module can also send SMS.

RS-485 pollingPer-point conditionsEmail, LINE, SMS
WHAT IS MONITORED

What this station needs to monitor

A small pumping station is usually unattended, so the first things you want to know remotely are the water level, whether the pumps are running and whether the power supply is normal.

Connected deviceConnectionReadings
Water level sensors (forebay and outer water level)
RS-485 ModbusWater level
Power meter (pump circuit)
RS-485 ModbusVoltage, current, energy use
Pump run and trip signals
External DI moduleRunning/stopped, fault contact
Float switches
External DI moduleHigh/low level contacts
CELLULAR

Optional cellular module (4G/5G) + antenna

LLD-4G-A mini-PCIe 4G module installed in the board’s expansion slot, with the antenna cable attached
  • No network cable needed

    Data goes over the 4G/5G cellular network via MQTT to the cloud or your own platform. SIM card not included.

  • SMS alerts

    When a reading goes outside the limits you set, CGate can also send an SMS directly, alongside email, LINE or other messaging.

  • Antenna included; takes an extension cable

    If the signal inside the panel is weak, an extension cable can take the antenna outside the panel. The extension cable is supplied separately to suit the site.

DEVICES

Devices used

CGate-05/06 gateway

GATEWAY
  • Polls RS-485 Modbus devices such as water level sensors and power meters, and keeps history in its built-in database
  • Web monitoring interface, plus notifications by email, LINE or other messaging
  • Sends data to host systems over Modbus TCP, MQTT or MySQL
View CGate products

Cellular module

OPTION
  • Fitted to CGate-05/06 with an antenna, it lets a site with no network cable send data back wirelessly and send SMS
  • SIM card not included
View the cellular module

Water level sensors, power meters and switch signals

FIELD DEVICES
  • Water level sensors and power meters connect over RS-485
  • Switch signals such as pump run, trip and float switches are read into CGate through an external DI module
FAQ

Common questions before you start

The pumping station’s equipment room after dark, its door open and the light showing the control panel inside, with the antenna at the corner of the roof

Will data be lost when the signal is poor?

No. CGate keeps polling while the connection is down and stores the data on the device, so you can view or export it in the web interface afterwards. The connection is restored automatically when the signal comes back, but data logged while it was down is not sent to the remote platform automatically.

Will I still get notifications during a power outage?

When the whole area loses power, CGate loses power too and cannot send a notification itself. Only the server that receives the data can tell: if no data arrives from the site for a while, the site has lost power or its connection, and someone needs to go and check.

Can it feed our existing monitoring platform?

Yes. CGate can output over Modbus TCP, MQTT (JSON) and MySQL at the same time, and you decide where the data goes. CGate gets the field data out; it does not replace your existing PLC or SCADA.

Without a static IP on the cellular connection, can our platform still get the data?

Yes. Cellular connections usually have no static IP, so outside systems cannot easily connect in to the site. CGate polls on site and pushes the data out over MQTT to the cloud or your platform, so nothing needs to connect in from outside.

Can switch signals such as pump run status and float switches be connected?

Yes, through our RIO remote I/O module. Switch signals such as pump run, trip and float switches are wired to RIO’s digital inputs (DI), and CGate reads them over RS-485 Modbus. CGate itself has no 4~20mA analog input; instruments with only an analog output can be connected through RIO’s analog inputs (AI) instead.

Do I need to get a SIM card separately?

Yes. The SIM card is not included: get one from a mobile carrier and insert it.

Can the antenna be extended?

Yes. The antenna supplied with the unit is a small one that screws directly onto the enclosure. If the signal inside the control panel is weak, an extension cable can take the antenna outside the panel. The extension cable is supplied separately to suit the site.

TAILORED TO YOUR SITE

Signal and equipment differ from site to site

The station’s instruments, the cellular signal on site and who gets notified all depend on the site. Send us your equipment list and register maps, and our sales team will help assess your needs.

Contact us